【Getek】 Pleat Panel Type-1175X585X83mm(472303)

Feature

1.You can choose to remove acid gas, alkaline gas or organic gas according to your needs, or two-in-one,three-in-one type.

2.Low pressure loss (100 Pa @ 2.5 m / sec), high air permeability, high initial efficiency (> 95%)

3.Long implantation, high adsorption capacity (6-24 months)

4.No doubt about outgassing (no organic gas and inorganic gas)

5.Low dust emission (ISO level 7 or higher)

6.
There are complete solutions for micro-pollution (AMC) and elimination of various odors/odors

7.
Suitable for air intake filter (MAU), return air filter (RCU) and fan filter (FFU) to provide a clean andclean air source

8.
It can be customized with medium dust filtering effect (MERV 8)

Item NO.

N O

PHA-472303-ABC  PAA-472303  PBA-472303 PCA-472303

SIZE

1175X585X83MM  (WxHxD)

Frame Material

AL

Target Gases

Acids, Bases & VOCs(H2S, SO2, HF, HCl, HBr, Cl2..)(NH3, Amines, NMP..), VOCs Molecular Acids(H2S, SO2, HF, HCl, HBr, Cl2,HNO3, H2SO4), VOCs, Dopants
Molecular Bases
(NH3, Amines, NMP..)
Molecular CondensablesVOCs (Benzene, Toluene,Xylene..), Ozone, Odors

Air Flow

  1080 (0.45 m/s)    

Initial Pressure Drop

  <15    

Initial Efficiency

  > 95%  

Test Report

Model No.PAA-472303